epoxy resin bushing

12 kV and 24 kV Epoxy Resin Bushing

709 words|Published On: 29/12/2025|

The following is the table of contents for this article.

Thanks for sharing the article.

Introduction

Epoxy resin bushings are widely used in medium-voltage switchgear, transformers, ring main units (RMUs), and solid insulated equipment. Their primary function is to safely pass a live conductor through a grounded enclosure while maintaining adequate electrical insulation.

Two key insulation parameters define bushing performance:

  • Clearance (air insulation distance)

  • Creepage distance (surface insulation distance)

Correct design of these distances is critical for preventing flashover, partial discharge, and long-term insulation failure, especially under polluted or humid conditions.


Key Definitions

Clearance (Insulation Distance)

Clearance is the shortest distance through air between live parts and earth or between phases.

It determines the ability to withstand:

  • Power-frequency voltage

  • Lightning impulse overvoltage


Creepage Distance

Creepage distance is the shortest distance along the surface of the insulation between live parts and earth.

It is mainly affected by:

  • Pollution level

  • Moisture

  • Surface contamination

  • Insulation material

For epoxy resin bushings, creepage distance is often the design-limiting factor.


Applicable IEC Standards

Epoxy resin bushing insulation design typically follows:

  • IEC 62271-1 – Common specifications

  • IEC 62271-200 – Metal-enclosed switchgear

  • IEC 60071 – Insulation coordination

  • IEC 60815 – Creepage distance in polluted environments


Rated Voltage and Insulation Levels

Rated VoltageHighest System VoltageLightning Impulse WithstandPower Frequency Withstand
12 kV12 kV75 kV28 kV
24 kV24 kV125 kV50 kV

These insulation levels directly influence minimum clearance requirements.


Clearance Requirements for Epoxy Resin Bushings

Typical Phase-to-Earth Clearance

Rated VoltageMinimum Clearance (mm)Typical Design Practice
12 kV≥ 125 mm125–150 mm
24 kV≥ 220 mm220–250 mm

Notes:

  • Values assume indoor, controlled environment

  • Outdoor or high-altitude installations require increased clearance

  • Solid insulation can reduce air clearance compared with air-insulated bushings, but safety margins are still applied


Phase-to-Phase Clearance

Rated VoltageMinimum Phase-Phase Clearance
12 kV≥ 145 mm
24 kV≥ 260 mm

Phase-phase clearance is usually slightly larger than phase-earth.


Creepage Distance Requirements (Epoxy Resin)

Creepage distance depends strongly on pollution severity, as defined in IEC 60815.

Typical Creepage Distance per kV

For epoxy resin insulation:

Pollution LevelCreepage Distance
Light16 mm/kV
Medium20 mm/kV
Heavy25 mm/kV
Very Heavy31 mm/kV

12 kV Epoxy Resin Bushing Creepage

Pollution LevelMinimum Creepage Distance
Light≥ 190 mm
Medium≥ 240 mm
Heavy≥ 300 mm
Very Heavy≥ 370 mm

Most indoor switchgear uses medium pollution as the design basis.


24 kV Epoxy Resin Bushing Creepage

Pollution LevelMinimum Creepage Distance
Light≥ 380 mm
Medium≥ 480 mm
Heavy≥ 600 mm
Very Heavy≥ 740 mm

For outdoor or coastal environments, heavy or very heavy pollution values are mandatory.


Why Epoxy Resin Allows Compact Design

Compared with porcelain or air-insulated bushings, epoxy resin offers:

  • Higher dielectric strength

  • Uniform insulation structure

  • Better resistance to moisture ingress

  • Improved partial discharge performance

This allows shorter clearances, but creepage distance cannot be reduced excessively, because surface pollution still governs flashover risk.


Design Features Used to Achieve Creepage Distance

Epoxy resin bushings typically use:

  • Multiple sheds or ribs

  • Optimized shed profile

  • Hydrophobic surface treatment

  • Smooth, defect-free molding

These features increase effective creepage without excessive height.

Indoor vs Outdoor Requirements

Indoor Switchgear Bushings

  • Lower pollution level

  • Smaller creepage acceptable

  • Focus on clearance and impulse withstand

Outdoor Bushings

  • High pollution exposure

  • Longer creepage mandatory

  • UV and weather resistance required

Outdoor epoxy bushings are often oversized compared with indoor types.


Altitude Correction

At altitudes above 1000 m, air density decreases.

Impact:

  • Clearance must be increased

  • Creepage remains unchanged

Typical correction:

  • Increase clearance by 1% per 100 m above 1000 m


Common Design Mistakes

  • Using indoor creepage values for outdoor installations

  • Ignoring pollution severity

  • Over-reducing clearance due to solid insulation

  • Poor shed profile causing water bridging

  • Inadequate quality control of epoxy casting

These mistakes significantly increase flashover risk.


Practical Selection Guidelines

When specifying epoxy resin bushings:

  • Confirm system highest voltage

  • Define installation environment

  • Apply correct pollution level

  • Check IEC compliance

  • Coordinate with switchgear insulation design

Never rely solely on “rated voltage” without creepage verification.


Summary Table

Parameter12 kV24 kV
Min clearance (phase-earth)≥ 125 mm≥ 220 mm
Typical creepage (medium pollution)≥ 240 mm≥ 480 mm
Common applicationIndoor MV switchgearUtility distribution
Insulation materialEpoxy resinEpoxy resin

Conclusion

For 12 kV and 24 kV epoxy resin bushings, correct insulation design requires careful coordination of clearance and creepage distance. While epoxy resin enables compact, solid-insulated solutions, creepage distance remains governed by pollution severity and IEC standards.

Properly designed bushings ensure:

  • High dielectric reliability

  • Resistance to pollution and moisture

  • Long service life

  • Compliance with utility and international standards

Correct insulation distance design is therefore a foundation of safe and durable medium-voltage equipment.

Recent Articles

Wind Substation Equipment: Types, Functions, and Selection Guide

Wind substation equipment plays a critical role in collecting, transforming, protecting, and transmitting electricity generated by wind turbines. From medium-voltage (MV) switchgear and power transformers to high-voltage (HV) equipment, protection [...]

Future-Proof Switchgear: Design, Selection, and Long-Term Reliability

Future-proof switchgear is designed and selected to accommodate changing electrical loads, evolving technologies, operational requirements, and future expansion with minimal disruption. For industrial facilities, commercial buildings, utilities, renewable energy projects, [...]

Send Your Inquiry