12 kV and 24 kV Epoxy Resin Bushing
The following is the table of contents for this article.
Thanks for sharing the article.
Introduction
Epoxy resin bushings are widely used in medium-voltage switchgear, transformers, ring main units (RMUs), and solid insulated equipment. Their primary function is to safely pass a live conductor through a grounded enclosure while maintaining adequate electrical insulation.
Two key insulation parameters define bushing performance:
Clearance (air insulation distance)
Creepage distance (surface insulation distance)
Correct design of these distances is critical for preventing flashover, partial discharge, and long-term insulation failure, especially under polluted or humid conditions.
Key Definitions
Clearance (Insulation Distance)
Clearance is the shortest distance through air between live parts and earth or between phases.
It determines the ability to withstand:
Power-frequency voltage
Lightning impulse overvoltage
Creepage Distance
Creepage distance is the shortest distance along the surface of the insulation between live parts and earth.
It is mainly affected by:
Pollution level
Moisture
Surface contamination
Insulation material
For epoxy resin bushings, creepage distance is often the design-limiting factor.
Applicable IEC Standards
Epoxy resin bushing insulation design typically follows:
IEC 62271-1 – Common specifications
IEC 62271-200 – Metal-enclosed switchgear
IEC 60071 – Insulation coordination
IEC 60815 – Creepage distance in polluted environments
Rated Voltage and Insulation Levels
| Rated Voltage | Highest System Voltage | Lightning Impulse Withstand | Power Frequency Withstand |
|---|---|---|---|
| 12 kV | 12 kV | 75 kV | 28 kV |
| 24 kV | 24 kV | 125 kV | 50 kV |
These insulation levels directly influence minimum clearance requirements.
Clearance Requirements for Epoxy Resin Bushings
Typical Phase-to-Earth Clearance
| Rated Voltage | Minimum Clearance (mm) | Typical Design Practice |
|---|---|---|
| 12 kV | ≥ 125 mm | 125–150 mm |
| 24 kV | ≥ 220 mm | 220–250 mm |
Notes:
Values assume indoor, controlled environment
Outdoor or high-altitude installations require increased clearance
Solid insulation can reduce air clearance compared with air-insulated bushings, but safety margins are still applied
Phase-to-Phase Clearance
| Rated Voltage | Minimum Phase-Phase Clearance |
|---|---|
| 12 kV | ≥ 145 mm |
| 24 kV | ≥ 260 mm |
Phase-phase clearance is usually slightly larger than phase-earth.
Creepage Distance Requirements (Epoxy Resin)
Creepage distance depends strongly on pollution severity, as defined in IEC 60815.
Typical Creepage Distance per kV
For epoxy resin insulation:
| Pollution Level | Creepage Distance |
|---|---|
| Light | 16 mm/kV |
| Medium | 20 mm/kV |
| Heavy | 25 mm/kV |
| Very Heavy | 31 mm/kV |
12 kV Epoxy Resin Bushing Creepage
| Pollution Level | Minimum Creepage Distance |
|---|---|
| Light | ≥ 190 mm |
| Medium | ≥ 240 mm |
| Heavy | ≥ 300 mm |
| Very Heavy | ≥ 370 mm |
Most indoor switchgear uses medium pollution as the design basis.
24 kV Epoxy Resin Bushing Creepage
| Pollution Level | Minimum Creepage Distance |
|---|---|
| Light | ≥ 380 mm |
| Medium | ≥ 480 mm |
| Heavy | ≥ 600 mm |
| Very Heavy | ≥ 740 mm |
For outdoor or coastal environments, heavy or very heavy pollution values are mandatory.
Why Epoxy Resin Allows Compact Design
Compared with porcelain or air-insulated bushings, epoxy resin offers:
Higher dielectric strength
Uniform insulation structure
Better resistance to moisture ingress
Improved partial discharge performance
This allows shorter clearances, but creepage distance cannot be reduced excessively, because surface pollution still governs flashover risk.
Design Features Used to Achieve Creepage Distance
Epoxy resin bushings typically use:
Multiple sheds or ribs
Optimized shed profile
Hydrophobic surface treatment
Smooth, defect-free molding
These features increase effective creepage without excessive height.
Indoor vs Outdoor Requirements
Indoor Switchgear Bushings
Lower pollution level
Smaller creepage acceptable
Focus on clearance and impulse withstand
Outdoor Bushings
High pollution exposure
Longer creepage mandatory
UV and weather resistance required
Outdoor epoxy bushings are often oversized compared with indoor types.
Altitude Correction
At altitudes above 1000 m, air density decreases.
Impact:
Clearance must be increased
Creepage remains unchanged
Typical correction:
Increase clearance by 1% per 100 m above 1000 m
Common Design Mistakes
Using indoor creepage values for outdoor installations
Ignoring pollution severity
Over-reducing clearance due to solid insulation
Poor shed profile causing water bridging
Inadequate quality control of epoxy casting
These mistakes significantly increase flashover risk.
Practical Selection Guidelines
When specifying epoxy resin bushings:
Confirm system highest voltage
Define installation environment
Apply correct pollution level
Check IEC compliance
Coordinate with switchgear insulation design
Never rely solely on “rated voltage” without creepage verification.
Summary Table
| Parameter | 12 kV | 24 kV |
|---|---|---|
| Min clearance (phase-earth) | ≥ 125 mm | ≥ 220 mm |
| Typical creepage (medium pollution) | ≥ 240 mm | ≥ 480 mm |
| Common application | Indoor MV switchgear | Utility distribution |
| Insulation material | Epoxy resin | Epoxy resin |
Conclusion
For 12 kV and 24 kV epoxy resin bushings, correct insulation design requires careful coordination of clearance and creepage distance. While epoxy resin enables compact, solid-insulated solutions, creepage distance remains governed by pollution severity and IEC standards.
Properly designed bushings ensure:
High dielectric reliability
Resistance to pollution and moisture
Long service life
Compliance with utility and international standards
Correct insulation distance design is therefore a foundation of safe and durable medium-voltage equipment.
Wind Substation Equipment: Types, Functions, and Selection Guide
Wind substation equipment plays a critical role in collecting, transforming, protecting, and transmitting electricity generated by wind turbines. From medium-voltage (MV) switchgear and power transformers to high-voltage (HV) equipment, protection [...]
Solar Farm Switchgear: Selection, Design, and Application Guide
Solar farm switchgear is an essential part of the electrical infrastructure used to collect, control, protect, and distribute power generated by photovoltaic (PV) systems. From inverter output circuits and transformer [...]
Future-Proof Switchgear: Design, Selection, and Long-Term Reliability
Future-proof switchgear is designed and selected to accommodate changing electrical loads, evolving technologies, operational requirements, and future expansion with minimal disruption. For industrial facilities, commercial buildings, utilities, renewable energy projects, [...]